Datasheet Content
BRUCIATORI MISTI DI GAS/GASOLIO BISTADIO
DUAL FUEL GAS/LIGHT-OIL BURNERS AT TWO STAGES SK073516_A_gb
[K X5/2]
K X5/2
Dual fuel gas/light-oil burners at two stages.
Composed by: aluminium frame, fan at high pressurisation and combustion head with adjustment at high efficiency
and high flame stability.
Compact overall dimensions and disposition rationalized of the components with accessibility facilitated for the
operations of setting and maintenance.
Available in the versions METHANE (natural gas) or L.P.G. (to specify at the order) on demand specific versions for
town gas, coal gas or biogas.
Gas train complete of: one-block valve class A (1st stage + 2nd stage slow opening + safety), minimum gas
pressure switch and filter-stabilizer.
Complete of: flange and gasket for installation on generator, nozzles, flexible pipes and line filter.
Fig. 1 K X5/2
K X5/2
DUAL FUEL GAS/LIGHT-OIL BURNERS AT TWO STAGES SK073516_A_gb
[K X5/2]
TECHNICAL DATA AND OPERATING RANGE DIAGRAM K X5/2
MODEL K X5/2
Thermal power 1°st. / min. 2°st. - max. 2°st. * [Mcal/h] 120.4/352.6-731
Thermal power 1°st. / min. 2°st. - max. 2°st. * [kW] 140/410-850
Gas flow G20 (NATURAL GAS) 1°st. / min. 2°st. - max. 2°st. * [Nm³/h] 14/41.1-85.2
Gas flow G31 (L.P.G.) 1°st. / min. 2°st. - max. 2°st. * [Nm³/h] 5.4/15.9-33
Fuel: NATURAL GAS (second family) - L.P.G. (third family)
Fuel category: I2R,I2H,I2L,I2E,I2E+,I2Er,I2ELL,I2E(R)
I3B/P,I3+,I3P,I3B,I3R
Minimum pressure gas train D1" - S NATURAL GAS/LPG ** [mbar] 72/53
Minimum pressure gas train D1"1/4 - S NATURAL GAS/LPG ** [mbar] 45/34
Minimum pressure gas train D1"1/2 - S NATURAL GAS/LPG ** [mbar] 28/23
Minimum pressure gas train D2" - S NATURAL GAS/LPG ** [mbar] 33/60
Maximum pressure at the entry of valves (Pe. max) [mbar] 360
LIGHT-OIL flow 1°st. / min. 2°st. - max. 2°st. * [kg/h] 11.8/34.6-71.6
Fuel: LIGHT-OIL 1,5°E at 20°C= 6,2 cSt = 35 sec Redwood N°1
Intermitted working operation (min. 1 stop every 24 hours) two stages
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60
Nominal electric power [kW] 2.0
Fan motor [kW] 1.5
Nominal absorption fan motor [A] 3.2
Pump motor [kW] 0.37
Nominal absorption pump motor [A] 1.2
Power supply: 3~400V, 1/N~230V-50Hz
Electric protection degree: IP 40
Burner weight [kg] 62
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Minimal feeding-gas pressure to the gas train to get the maximum power of the burner, considering counter-pressure in combustion chamber of
value 0 (zero).
[mbar]
[kW]
Fig. 2 X = Thermal power Y = Pressure in combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the
boiler. For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-
compliance, contact the manufacturer.
K X5/2
DUAL FUEL GAS/LIGHT-OIL BURNERS AT TWO STAGES SK073516_A_gb
[K X5/2]
DIMENSIONS [MM]
H
D
R1
G
S
RD B C TC-TL** E
R2 R4
R3 F1 - F2*
Fig. 3 Dimensions: K X5/2
MODEL A B C D E F1 F2* G H I L S R1 R2 R3 R4 RD Gas
train
weight
K X5/2 - D1"-S 300 245 388 175 122 794 1234 416 171 144 10 18 250 380 438 504 Rp1 23 kg
K X5/2 - D1"1/4-S 300 245 388 175 122 794 1234 416 171 144 10 18 250 380 438 504 Rp 1 1/4 23 kg
K X5/2 - D1"1/2-S 300 245 388 175 122 794 1234 416 171 144 10 18 250 380 430 520 Rp 1 1/2 25 kg
K X5/2 - D2"-S 300 245 388 175 122 794 1234 416 171 144 10 18 250 380 430 520 Rp 2 25 kg
F2*: Encumbrance with burner move back.
TC-TL**: see chapter "FLAME TUBE LENGTH"
BOILER PLATE
*** Suggested dimension of connection between
burner and generator.
Fig. 4 Boiler plate
MODEL L min L max M N min N * * * N
max
K X5/2 mm 310 368 M12 185 185 250
FLAME TUBE LENGTH
Flame tube length must be selected based on the specifications supplied by boiler manufacturer and, in any case, it
must be greater than the thickness of the boiler door included its insulation. In case of boilers with flame inversion or
front flue combustion chambers, it is necessary to insulate the area between the flame tube and front door with
refractory material. This protection material must not impede flame tube extraction.
MODEL TC TL ****
K X5/2 mm 250 315
**** For different flame lengths, please contact our Technical-Sales Department.
K X5/2
DUAL FUEL GAS/LIGHT-OIL BURNERS AT TWO STAGES SK073516_A_gb
[K X5/2]
PRODUCT SPECIFICATION
SHORT DESCRIPTION
Dual fuel gas/light-oil burners at two stages.
DETAILED SPECIFICATION
Dual fuel gas/light-oil burners at two stages, composed by:
• Aluminium frame;
• Fan at high pressurisation;
• Combustion head with adjustment at high performance and elevated flame stability equipped with blast tube and flame disc;
• Flange and insulating gasket for fixing at boiler;
• Three-phase power supply;
• Manual switch for the fuel selection gas/light-oil;
• Safety air pressure switch to stop the burner in lock-out in case of failed or anomalous fan operation;
• Equipped with gas train with one-block valve class A (1st stage + 2nd stage slow opening + safety); gas pressure switch and
stabilizer filter;
• Gas valve proving system VPS asoptional;
• Motor dedicated for the light-oil pump; it turns on simultaneously to the ignition transformer activation;
• Maximum gas pressure switch asoptional;
• UV probe for flame detection;
• Supports and tierods for burner extraction;
• Servomotor for air shutter and for the consent of the 2nd stage operation;
• Moving shutter with total closure when idle in order to reduce at the least energy losses related to boiler cooling down;
• IP 40 electric protection level.
CONFORMING TO:
• CE rules;
• 2014/30/UE Directive E.M.C.;
• 2014/35/UE Directive LVD;
• 2006/42/CE - 2006/42/EG - 2006/42/EC Directive MD;
• Directive PED (art.4, par.3) 2014/68/EU;
• Reference rules: EN676 (gas) - EN267 (liquid fuel) - EN746-2 (industrial thermoprocessing equipment).
STANDARD EQUIPMENT
• Flexible pipes;
• Line filter;
• Isomart gasket;
• Nozzles;
• Flange with insulating gasket;
• Burner nameplate;
• Warranty;
• Instruction handbook for installation, use and maintenance.
OPTIONAL
• Noiseprotection;
• Antivibrationcouplings;
• Handlegastaps.
The illustrations and data here shown are indicative. F.B.R. Bruciatori S.r.l. reserves the right to bring, without any obligation of warning, any changes that would be appropriate to the continuing development of their products.
K X5/2