Datasheet Content
LIGHT-OIL BURNERS TWO STAGES
FGP 130/2 EVO - FGP 160/2
Light-oil burners two stages.
Composed by: fan at high pressurisation, combustion head with adjustment at high efficiency and high
flame stability and hydraulic system of regulation combustive air on the two stages of flame.
The burners are equipped with two motors : air blower motor + pump motor.
Compact overall dimensions and disposition rationalized of the components with accessibility facilitated
for the operations of setting and maintenance.
Complete of 2 nozzles, 2 flexible hoses and line filter.
Complete of flange and gasket for installation on generator.
FGP 130/2 EVO - FGP 160/2
LIGHT-OIL BURNERS TWO STAGES
TECHNICAL DATA FGP 130/2 EVO
MODEL FGP 130/2 EVO
Flow min. 1°st. / min. 2°st. - max. 2°st. * [kg/h] 28.3/60-130
Thermal power min. 1°st. / min. 2°st. -
[Mcal/h] 289/612-1326
max. 2°st. *
Thermal power min. 1°st. / min. 2°st. -
[kW] 336/712-1542
max. 2°st. *
Fuel: LIGHT-OIL 1.5°E at 20°C = 6.2 cSt = 35 sec Redwood N°1
Intermitted working operation (min. 1 stop every 24 hours) two stages
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60
Nominal electric power [kW] 3
Fan motor [kW] 2.2
Pump motor [kW] 0.37
Nominal fan motor current absorption [A] 4.35
Nominal pump motor current absorption [A] 1.2
Nominal auxiliary absorption [A] 0.82
Power supply: 3~400V, 1N~230V - 50Hz
Electric protection degree: IP 40
Noisiness ** min-max [dBA] 83.8-84
Weight *** [kg] 84
* Reference conditions : Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Measured sonourous pressure in the combustion lab, with funcional burner on beta boiler in a distance of 1 m (UNI EN ISO 3746).
*** For burner with long head add 2 kg.
OPERATING RANGE DIAGRAM FGP 130/2 EVO
[mbar] 18
16
14
12
10
8
6
4
2
0
200 400 600 800 1000 1200 1400 1600 [kW]
Fig. X = Therma l power Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the boiler.
For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-compliance,
contact the manufacturer.
FGP 130/2 EVO - FGP 160/2
LIGHT-OIL BURNERS TWO STAGES
TECHNICAL DATA FGP 160/2
MODEL FGP 160/2
Flow min. 1°st. / min. 2°st. - max. 2°st. * [kg/h] 36.7/75-160
Thermal power min. 1°st. / min. 2°st. -
[Mcal/h] 374/765-1634
max. 2°st. *
Thermal power min. 1°st. / min. 2°st. -
[kW] 435/889-1900
max. 2°st. *
Fuel: LIGHT-OIL 1.5°E at 20°C = 6.2 cSt = 35 sec Redwood N°1
Intermitted working operation (min. 1 stop every 24 hours) two stages
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60
Nominal electric power [kW] 5
Fan motor [kW] 4
Pump motor [kW] 0.37
Nominal fan motor current absorption [A] 7.45
Nominal pump motor current absorption [A] 1.2
Nominal auxiliary absorption [A] 0.82
Power supply: 3~400V, 1N~230V - 50Hz
Electric protection degree: IP 40
Noisiness ** min-max [dBA] 84.4-85.4
Weight *** [kg] 95
* Reference conditions :Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Measured sonourous pressure in the combustion lab, with funcional burner on beta boiler in a distance of 1 m (UNI EN ISO 3746).
*** For burner with long head add 2 kg.
OPERATING RANGE DIAGRAM FGP 160/2
[mbar] 18
16
14
12
10
8
6
4
2
0
200 400 600 800 1000 1200 1400 1600 1800 2000 [kW]
Fig. X = Therma l power Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the boiler.
For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-compliance,
contact the manufacturer.
FGP 130/2 EVO - FGP 160/2
LIGHT-OIL BURNERS TWO STAGES
DIMENSIONS [MM]
G
F
H C
I E
A B TC - TL * D1-D2
J
K
Fig. Dimensions FGP 130/2 EVO - FGP 160/2
MODEL A B C D1 D2 E F G H I J K
FGP 130/2 EVO 383 343 209 803 1383 510 211 320 320 20 183 40
FGP 160/2 383 405 209 803 1383 510 211 320 320 20 183 40
* see "flame tube length"
D2: Overall dimension with the burner out in position of maintenance.
FGP 130/2 EVO - FGP 160/2
LIGHT-OIL BURNERS TWO STAGES
BOILER PLATE
* Suggested dimension of connection between burner
and generator.
Fig. Boiler plate
MODEL L min L max M N min N* N max
FGP 130/2 EVO mm 340 368 M14 230 230 250
FGP 160/2 mm 340 368 M14 230 230 250
FLAME TUBE LENGTH
Flame tube length must be selected based on the specifications supplied by boiler manufacturer and, in any case, it
must be greater than the thickness of the boiler door included its insulation.
In case of boilers with flame inversion or front flue combustion chambers, it is necessary to insulate the area between
the flame tube and front door with refractory material. This protection material must not impede flame tube extraction.
MODEL TC TL **
FGP 130/2 EVO mm 210 400
FGP 160/2 mm 210 400
** For different flame lengths, please contact our Technical-Sales Department.
FGP 130/2 EVO - FGP 160/2
LIGHT-OIL BURNERS TWO STAGES
BURNER SIGNAL DESCRIPTION
In the picture below there are indicated all the signalation present on the burner:
1
2
Fig. Burner signal description
LEGEND
1) ON/OFF button
2) Reset from lockout button + status lamp
The multicolor signal lamp in the lockout reset button (pos.2) is the key indicating element for visual diagnostics
and interface diagnostics.
In normal operation, the different operating states are indicated in the form of color codes; please refer to
electrical device handbook supplied with the present instructions.
After a non-alterable lockout, the red signal lamp in the lockout reset button (pos.2) lights up.
By pressing the lockout reset button (pos.2) for more than 3 seconds, the visual diagnostics of the cause of fault
can be activated; please refer to electrical device handbook supplied with the present instructions.
For close the diagnostics mode and for switch on the burner again, it is necessary to reset the burner control.
Press the lockout reset button (pos.2) for about 1 second (<3 seconds).
After a non-alterable lockout, the red signal lamp in the lockout reset button (pos.2) lights up.
For reset the control box press the lockout reset button (pos.2) for about 1 second (<3 seconds).
FGP 130/2 EVO - FGP 160/2
LIGHT-OIL BURNERS TWO STAGES
PRODUCT SPECIFICATION
SHORT DESCRIPTION
Light-oil burners two stages.
DETAILED SPECIFICATION
Light-oil burner two stages composed by:
• Fan at high pressurisation at reverse blades FGP130/2 EVO;
• Fan at high pressurisation FGP160/2;
• Combustion head with adjustment at high performance and elevated flame stability;
• Flange and…