Datasheet Content
LIGHT-OIL BURNERS ONE STAGE SERIES LX SK070061_A_en
LIGHT-OIL BURNERS ONE STAGE SERIES LX
G 0SR-LX - G 0S-LX - G 0H-LX - G 1SR-LX - G 1S-LX - G 1H-LX
Light-oil burners single stage - Low NOx (NOx < 120 mg/kWh).
They are composed by: aluminium frame, protection cover with noise reduction plate, combustion head with
micrometric adjustment, high flame stability and low emissions.
Compact overall dimensions and disposition rationalized of the components with accessibility facilitated for the
operations of setting and maintenance.
In the versions H hydraulic device of closing air shutter.
In the versions R preheater with control of temperature for soft and sicure ignitions also at low temperatures.
Complete of connector 7 poles, flange and gasket for installation on boiler, nozzle, flexible pipes, line filter.
Fig. 1 G 0SR-LX - G 0S-LX - G 0H-LX
Fig. 2 G 1SR-LX - G 1S-LX - G 1H-LX
G 0SR-LX - G 0S-LX - G 0H-LX - G 1SR-LX - G 1S-LX - G 1H-LX
LIGHT-OIL BURNERS ONE STAGE SERIES LX SK070061_A_en
TECHNICAL DATA G 0SR-LX - G 0S-LX - G 0H-LX - G 1SR-LX - G 1S-LX - G 1H-LX
MODEL G 0SR-LX G 0S-LX G 1SR-LX G 1S-LX
G 0H-LX G 1H-LX
Flow min. - max. * [kg/h] 1.8-3.3 1.8-3.3 2.7-5.0 2.7-5.0
Thermal power min. - max. * [Mcal/h] 18.4-33.7 18.4-33.7 27.5-51 27.5-51
Thermal power min. - max. * [kW] 21.3-39 21.3-39 31.9-59.2 31.9-59.2
Fuel: LIGHT-OIL 1.5°E at 20°C = 6.2 cSt = 35 sec Redwood N°1
NOx [mg/kWh]
Intermitted working operation (min. 1 stop every 24 hours) one stage
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60
Nominal electric power [W] 190 120 220 130
Fan motor [W] 90 90 100 100
Nominal current absorption [A] 0.9 0.6 1 0.6
Pre-heater [W] 30-110 - 30-110 -
Power supply: 1N~230V - 50Hz
Electric protection degree: IP 40
Noisiness min. - max. ** [dBA] 56-58 56-58 57-59 57-59
Burner weight *** [kg] 8 8 10 10
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Measured sonorous pressure in the combustion laboratory, with burner on operation on beta boiler to 1m of distance (UNI EN ISO 3746).
*** For burner with iron cover (F) add 3 kg to the weight.
OPERATING RANGE DIAGRAM G 0SR-LX - G 0S-LX - G 0H-LX - G 1SR-LX - G 1S-LX - G 1H-LX
Fig. 3 X = Thermal power Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the boiler.
For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-compliance,
contact the manufacturer.
G 0SR-LX - G 0S-LX - G 0H-LX - G 1SR-LX - G 1S-LX - G 1H-LX
LIGHT-OIL BURNERS ONE STAGE SERIES LX SK070061_A_en
DIMENSIONS [MM]
Fig. 4 Dimensions G 0SR-LX - G 0S-LX - G 0H-LX - G 1SR-LX - G 1S-LX - G 1H-LX
MODEL A B C D E F G H I
G0...-LX 137 137 240 80 223 169 15 150 150
G1...-LX 157 170 275 90 265 210 15 150 150
* See "flame tube length"
BOILER PLATE
* Suggested dimension of connection between burner
and generator.
Fig. 5 Boiler plate
MODEL L min L* L max M N min N* N max
G0...-LX mm 130 150 170 M8 90 110 130
G1...-LX mm 130 150 170 M8 90 110 130
FLAME TUBE LENGTH
Flame tube length must be selected based on the specifications supplied by boiler manufacturer and, in any case, it
must be greater than the thickness of the boiler door included its insulation.
In case of boilers with flame inversion or front flue combustion chambers, it is necessary to insulate the area between
the flame tube and front door with refractory material. This protection material must not impede flame tube extraction.
MODEL TXC TC TL **
G0...-LX mm 85 110 130
G1...-LX mm - 110 130
** For different flame lengths, please contact our Technical-Sales Department.
G 0SR-LX - G 0S-LX - G 0H-LX - G 1SR-LX - G 1S-LX - G 1H-LX
LIGHT-OIL BURNERS ONE STAGE SERIES LX SK070061_A_en
PRODUCT SPECIFICATION
SHORT DESCRIPTION
Light-oil burners one stage - Low NOx (NOx < 120 mg/kWh).
DETAILED SPECIFICATION
Light-oil burner one stage - Low NOx (NOx < 120 mg/kWh) composed by:
• Aluminium frame;
• Combustion head with micrometric adjustment, high flame stability and low emissions;
• Protection cover with noise reduction plate;
• Flange and insulating gasket for fixing at boiler;
• Single-phase power supply;
• Photoresistance for flame detection;
• IP 40 electric protection level.
CONFORMING TO:
• CE rules;
• 2014/30/UE Directive E.M.C.;
• 2014/35/UE Directive L.V.;
• 2014/68/EU Directive M.D.;
• 97/23/CE Directive P.E.D.;
• Reference rules: EN267 (liquid fuel) - EN746-2 (industrial thermoprocessing equipment).
STANDARD EQUIPMENT
• Flexible hoses for connection;
• Line filter;
• Isomart gasket;
• Nozzle;
• Flange with insulating gasket;
• Burner nameplate;
• Warranty;
• Instruction handbook for installation, use and maintenance.
The illustrations and data here shown are indicative. F.B.R. Bruciatori S.r.l. reserves the right to bring, without any obligation of warning, any changes that would be appropriate to the continuing development of their products.
G 0SR-LX - G 0S-LX - G 0H-LX - G 1SR-LX - G 1S-LX - G 1H-LX