APPLICATION
EURO-OIL CONTROLS This range of electronic oil burner controls has been specifically
designed for oil burners for non permanent operation.
SERIES 10 The automatic burner controls of this series are suitable for:
− monobloc oil burners;
AUTOMATIC OIL BURNER CONTROL − power washers;
SYSTEM − warm air generators;
− steam boilers;
− kilns.
Due to the technical and structural characteristics and to the
variety of models they can be used for the automation of cookers
and oil burner operated appliances for domestic and industrial
applications.
FEATURES
Table 1 shows the main features of this series.
Other important features are:
− for non permanent operation;
− for fuel throughput < 30 kg/h (TSMAX = 10s) or fuel throughput
from 30 to 100 kg/h (TVmin = 15s e TSMAX = 5s);
− in accordance with the European standard concerning
monobloc oil burners and control systems DIN EN 230:2005;
− in compliance also with the standard DIN EN 13842:2004-10
for warm air generators (WLE, versions with TV = 20s e TS =
5s);
− two independent safety contacts for oil valve control;
− electrical service life at max load >250.000 operations;
− simple wiring and installation.
Table 1
Classification code according to EN 230
Normal operation in case of pre-heating
Flame detectors
thermostat opening External remote reset
Flame detectors
Single flame Dual flame Pre-heater On-board reset FC11/* FC13/* FC14/* FC14L/* Certificate N°.
Type FC7/* FC8/*
GR1 * (1) * * * FMCLXN 09 07 91305 002
GR1/Z * * * * * * FMCLXN 09 07 91305 002
GR2 * (1) * * * FTCLXN 09 07 91305 003
G22 * (1) * * FMCLXN 09 07 91305 001
G22/Z * * * * * FMCLXN 09 07 91305 001
GF2 * * * FTCLXN 09 07 91305 001
OR1 * (1) * * FMCLXN 09 07 91305 002
OR1/Z * * * * * FMCLXN 09 07 91305 002
OR2 * * * FTCLXN 09 07 91305 003
OR3/B * * * * FTCLXN 09 07 91305 003
NOTE:
1. this option is possible only by an external connection.
14710_r01 1/6
TECHNICAL DATA OVERALL DIMENSIONS
Supply voltage: 220÷240V∼ @ 50/60Hz The following figure (Fig.1) shows the overall dimensions of
On request: 110÷120V∼ @ 50/60Hz the control.
Operating temperature range: -20°C ÷ +60°C
Ambient humidity: 95% max @ 40°C
Protection degree: IP 40
Times:
1
- Prepurge time (TV) : 1,5 / 10 / 20 / 30 / 40 s
1
- Safety time (TS) : 5 / 10 s
- Dropout time on running flame failure: <1s
Power consumption:
- for supply voltage of 220÷240VAC: 8 VA
- for supply voltage of 110÷120VAC: 4 VA
Contact rating: Imax
- Room thermostat (T): 5,0 A cosϕ > 0,4
2
- Pre-heater thermostat (TC) : 4,5 A cosϕ > 0,4
- Pre-heater (RISC): 0,5 A cosϕ = 1,0
- Fan (MB): 2,0 A cosϕ > 0,4
- Ignition transformer (TR): 2,0 A cosϕ > 0,4
- First valve (EV1): 0,5 A cosϕ > 0,4
Fig. 1 – Overall dimensions
- Second valve (EV2): 0,5 A cosϕ > 0,4
- Alarm (SB): 1,0 A cosϕ = 1,0 CONNECTION
Maximum length of external components cables: For the connection of the external components the control
- Thermostats (T - TC): 20 m can be fitted either with socket type N (see Fig. 2), provided
- Reset and alarm (RE - SB): 10 m with a screw terminal board which allows a simple and safety
- All the others: 1m connection.
3 To fix the sockets it is advisable to use screws type M4. To
Switch-off voltage :…