We ship worldwide — Singapore, Australia, Malaysia, Indonesia, Philippines, India, Middle East & more

SIEMENS IEC

Siemens IEC supplementary protectors and miniature circuit breakers (MCBs) are designed for overcurrent protection in industrial control panels, machinery, and power distribution systems. The 5SY4 series, represented in the product range carried by 3G Electric, includes UL1077-listed supplementary protectors and UL489-listed miniature circuit breakers. These devices are DIN rail-mountable and feature screw-clamp terminals for secure wiring. Available in A-curve and D-curve trip characteristics, they cover a range of current ratings from 1.6 A to 50 A, with a voltage rating of 400 V AC and a DC rating of 72 V. The interrupting capacity is 10 kA at 400 V AC, suitable for branch circuit protection in commercial and light industrial applications. The A-curve devices are intended for resistive or lightly inductive loads where inrush currents are minimal, while the D-curve devices handle higher inrush currents typical of motors, transformers, and solenoid loads. The 2-pole and 4-pole configurations allow for single-phase and three-phase applications. Siemens, a global manufacturer of electrical and electronic equipment, produces these protectors under its IEC portfolio, which adheres to international standards for performance and safety. 3G Electric supplies these components to plant engineers, maintenance managers, and procurement specialists worldwide, ensuring availability of specific ratings and configurations for replacement or new installations. The product line supports applications in HVAC systems, conveyor drives, pump controls, and other industrial equipment requiring reliable overcurrent protection. The compact design and standardized mounting simplify panel layout and reduce installation time. All units are rated for use in pollution degree 2 environments and operate within a temperature range of -25°C to +55°C, as per typical Siemens specifications for the 5SY4 series. The screw-clamp terminals accept conductors up to 25 mm² for the larger current ratings, providing flexibility in wiring. The devices are marked with the CE and UL logos, indicating compliance with European and North American standards. For procurement, the MPN (e.g., 5SY42108) directly corresponds to the specific rating and curve, enabling accurate ordering. 3G Electric maintains stock of these protectors to support maintenance and project requirements without extended lead times.

Genuine
OEM Parts
Expert
Tech Support
1 Day
Quote Response
Worldwide
Origin
Worldwide Shipping
Air & sea freight
Datasheets on Request
Technical specs & drawings
1-Day Quote Response
Singapore-based team
Browse:
Show
Page 2 of 2
← Prev12Next →

About SIEMENS IEC

Siemens IEC supplementary protectors and miniature circuit breakers (MCBs) are designed for overcurrent protection in industrial control panels, machinery, and power distribution systems. The 5SY4 series, represented in the product range carried by 3G Electric, includes UL1077-listed supplementary protectors and UL489-listed miniature circuit breakers. These devices are DIN rail-mountable and feature screw-clamp terminals for secure wiring. Available in A-curve and D-curve trip characteristics, they cover a range of current ratings from 1.6 A to 50 A, with a voltage rating of 400 V AC and a DC rating of 72 V. The interrupting capacity is 10 kA at 400 V AC, suitable for branch circuit protection in commercial and light industrial applications. The A-curve devices are intended for resistive or lightly inductive loads where inrush currents are minimal, while the D-curve devices handle higher inrush currents typical of motors, transformers, and solenoid loads. The 2-pole and 4-pole configurations allow for single-phase and three-phase applications. Siemens, a global manufacturer of electrical and electronic equipment, produces these protectors under its IEC portfolio, which adheres to international standards for performance and safety. 3G Electric supplies these components to plant engineers, maintenance managers, and procurement specialists worldwide, ensuring availability of specific ratings and configurations for replacement or new installations. The product line supports applications in HVAC systems, conveyor drives, pump controls, and other industrial equipment requiring reliable overcurrent protection. The compact design and standardized mounting simplify panel layout and reduce installation time. All units are rated for use in pollution degree 2 environments and operate within a temperature range of -25°C to +55°C, as per typical Siemens specifications for the 5SY4 series. The screw-clamp terminals accept conductors up to 25 mm² for the larger current ratings, providing flexibility in wiring. The devices are marked with the CE and UL logos, indicating compliance with European and North American standards. For procurement, the MPN (e.g., 5SY42108) directly corresponds to the specific rating and curve, enabling accurate ordering. 3G Electric maintains stock of these protectors to support maintenance and project requirements without extended lead times.

Common Applications

  • Motor control centers — Siemens 5SY4 D-curve supplementary protectors (e.g., 5SY42108) for motor branch circuit protection
  • HVAC equipment — A-curve protectors (e.g., 5SY42255) for compressor and fan motor overcurrent protection
  • Industrial conveyor systems — 4-pole D-curve protectors (e.g., 5SY44168) for three-phase motor protection with neutral
  • Pump control panels — 2-pole supplementary protectors (e.g., 5SY42038) for single-phase pump motor protection
  • Machine tool control circuits — A-curve protectors (e.g., 5SY44155) for solenoid valve and relay protection
  • Power distribution sub-panels — 4-pole protectors (e.g., 5SY44155) for three-phase branch circuit protection in light industrial settings

Frequently asked questions

Common questions about SIEMENS IEC from 3G Electric.

What is the difference between A-curve and D-curve in Siemens IEC supplementary protectors?

The trip curve determines the instantaneous tripping threshold relative to the rated current. A-curve devices trip at 2 to 3 times the rated current, making them suitable for resistive loads or circuits with low inrush currents. D-curve devices trip at 10 to 20 times the rated current, designed for loads with high inrush currents such as motors, transformers, and solenoid valves. For example, a 10 A D-curve protector (MPN 5SY42108) will tolerate a brief inrush of up to 200 A before tripping, whereas an A-curve protector of the same rating would trip at 20-30 A. Choose the curve based on the load characteristics to avoid nuisance tripping.

Are Siemens 5SY4 series protectors UL489 or UL1077 listed?

The 5SY4 series includes both UL1077 supplementary protectors and UL489 miniature circuit breakers, depending on the specific model. The products listed in the 3G Electric catalog (e.g., SKU 30XU80, MPN 5SY42038) are UL1077 supplementary protectors. UL1077 devices are intended for use as supplementary overcurrent protection within equipment, not as branch circuit protection. They are suitable for industrial control panels, HVAC equipment, and machinery where the upstream branch circuit protection is already provided. For branch circuit protection, use UL489-listed MCBs. Always verify the listing on the device label or datasheet.

What is the maximum wire size that can be connected to the screw-clamp terminals of these Siemens protectors?

For the 5SY4 series supplementary protectors, the screw-clamp terminals accept conductors up to 25 mm² (approximately 4 AWG) for current ratings above 32 A. For lower current ratings (e.g., 1.6 A to 25 A), the terminal capacity is typically up to 16 mm² (6 AWG). The clamping torque is specified as 2.0-2.5 Nm for most models. Always refer to the product datasheet for exact specifications, as terminal capacity may vary by current rating. The terminals are designed for copper conductors only.

Can Siemens 5SY4 supplementary protectors be used in DC circuits?

Yes, the 5SY4 series supplementary protectors are rated for DC operation up to 72 V DC. This is indicated in the specifications for models such as the 5SY42038 (3 A, D-curve) and 5SY42108 (10 A, D-curve). The DC rating applies to both 2-pole and 4-pole configurations. For DC applications, ensure the polarity is observed and the device is used within its rated voltage and current limits. The interrupting capacity at DC may differ from the AC rating; consult the manufacturer's documentation for specific DC performance data.

What is the interrupting capacity of Siemens 5SY4 supplementary protectors?

The interrupting capacity for the 5SY4 series supplementary protectors is 10 kA at 400 V AC. This is consistent across the models listed, including the 3 A (5SY42038), 10 A (5SY42108), and 50 A (5SY42508) variants. The DC interrupting capacity is typically lower; for example, at 72 V DC, the rating may be 10 kA as well, but always verify with the specific product datasheet. This rating ensures the device can safely interrupt fault currents up to 10,000 amperes under short-circuit conditions.

What is the operating temperature range for Siemens 5SY4 supplementary protectors?

The Siemens 5SY4 series supplementary protectors are designed to operate within an ambient temperature range of -25°C to +55°C. This range covers typical industrial environments, including unheated enclosures and control panels. Storage temperature range is -40°C to +70°C. The devices are rated for pollution degree 2, meaning they are suitable for environments with only non-conductive pollution, such as typical control rooms and light industrial settings. For applications outside this range, consult Siemens for derating or alternative products.