GAS BURNERS AT SINGLE STAGE SK071010_2_B
GASBURNERSATSINGLESTAGE
GASXP60CEEVO
Burnersforgasatsinglestage.
Theyarecomposedby:fanathighpressurisationatreversebladesandcombustionheadwithadjustmentathigh
efficiencyandhighflamestability.
Compactoveralldimensionsanddispositionrationalizedofthecomponentswithaccessibilityfacilitatedforthe
operationsofsettingandmaintenance.
AvailableintheversionsMETHANE(naturalgas)orL.P.G.(tospecifyattheorder)ondemandspecificversionsfor
towngas,coalgasorbiogas.
Gastraincompleteofsingle-stageworkingvalvewithflowadjustment,safetyvalve,minimumgaspressureswitchand
gasfilter.
Completeofflangeandgasketforinstallationongenerator.
Fig. 1 GASXP60CEEVO
GAS XP60CE EVO
GAS BURNERS AT SINGLE STAGE SK071010_2_B
TECHNICAL DATA AND OPERATING RANGE DIAGRAM GAS XP60CE EVO
MODEL GAS XP60CE EVO
Thermalpowermin.-max.* [Mcal/h] 200-542
Thermalpowermin.-max.* [kW] 232-630
GasflowG20(NATURALGAS)min.-max.* [Nm³/h] 23.3-63.3
GasflowG31(L.P.G.)min.-max.* [Nm³/h] 9-24.5
Fuel:NATURALGAS(secondfamily)-L.P.G.(thirdfamily)
Fuelcategory: I2R,I2H,I2L,I2E,I2E+,I2Er,I2ELL,I2E(R)
I3B/P,I3+,I3P,I3B,I3R
Intermittedworkingoperation(min.1stopevery24hours)singlestage
Environmentalconditionsoperation/storage: -15...+40°C / -20...+70°C, rel. humidity max.
80%
Max.temperaturecombustionair [°C] 60
MinimumpressuregastrainD1"-SNATURALGAS/L.P.G.** [mbar] 115.3 / 60
MinimumpressuregastrainD1"1/4-SNATURALGAS/L.P.G.** [mbar] 54.5 / 37.4
MinimumpressuregastrainD1"1/2-SNATURALGAS/L.P.G.** [mbar] 17.7 / 21.8
Maximumpressureattheentryofvalves(Pe.max) [mbar] 360
Nominalelectricpower [W] 700
Fanmotor [W] 550
Nominalpowertabsorption [A] 1.4
Nominalauxiliaryabsorption [A] 0.5
Powersupply: 3~400V,1N~230V-50Hz
Electricprotectiondegree: IP 40
Noisiness***min.-max. [dB(A)] 69-72
Burnerweight**** [kg] 29.5
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Minimal feeding-gas pressure to the gas train to get the maximum power of the burner, considering counter-pressure in combustion chamber of
value 0 (zero).
*** Measured sonorous pressure in the laboratory combustion, with functional burner on beta boiler to 1 metre of distance (UNI EN ISO 3746 -
Metodo di controllo Classe 3 - La tolleranza sulla pressione sonora misurata può essere assunta pari a ± 1 [dB(A)]).
**** For burner with long head add 1 kg to the weight.
[mbar] 10
8
6
4
2
GAS XP60
0
-2
50 150 250 350 450 550 650 [kW]
Fig. 2 X = Thermal power Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the boiler.
For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-compliance,
contact the manufacturer.
GAS XP60CE EVO
GAS BURNERS AT SINGLE STAGE SK071010_2_B
DIMENSIONS [MM]
A
20
A H
D
R1
G
RD TC-TL E
B C R4
R2 F
R3
Fig. 3 Dimensions GAS XP60CE EVO
MODEL A B C D E F G H R1 R2 R3 R4 RD TC TL
GASXP60CEEVO-D1"-S 200 188 274 150 99 558 416 100 193 280 338 431 Rp 1 250 335
GASXP60CEEVO-D1"1/4-S 200 188 274 150 99 558 416 100 193 280 338 431 Rp 1 1/4 250 335
GASXP60CEEVO-D1"1/2-S 200 188 274 150 99 558 416 100 193 280 346 446 Rp 1 1/2 250 335
BOILER PLATE
* Suggested dimension of connection between burner
and generator.
Fig. 4 Boiler plate
MODEL L min L* L max M N min N* N max
GASXP60CEEVO mm 160 160 180 M10 205 205 226
FLAME TUBE LENGTH
Flame tube length must be selected based on the specifications supplied by boiler manufacturer and, in any case, it
must be greater than the thickness of the boiler door included its insulation.
In case of boilers with flame inversion or front flue combustion chambers, it is necessary to insulate the area between
the flame tube and front door with refractory material. This protection material must not impede flame tube extraction.
MODEL TC TL **
GASXP60CEEVO mm 250 335
** For different flame lengths, please contact our Technical-Sales Department.
GAS XP60CE EVO
GAS BURNERS AT SINGLE STAGE SK071010_2_B
BURNER SIGNAL DESCRIPTION
In the picture below there are indicated all the signalation present on the burner:
2 1
3
Fig. 5 Burner signal description
LEGEND
1) ON/OFF button
2) Reset from lockout button + status lamp
3) GAS valve lamp
The multicolor signal lamp in the lockout reset button (pos.2) is the key indicating element for visual diagnostics
and interface diagnostics.
In normal operation, the different operating states are indicated in the form of color codes; please refer to
electrical device handbook supplied with the present instructions.
After a non-alterable lockout, the red signal lamp in the lockout reset button (pos.2) lights up.
By pressing the lockout reset button (pos.2) for more than 3 seconds, the visual diagnostics of the cause of fault
can be activated; please refer to electrical device handbook supplied with the present instructions.
For close the diagnostics mode and for switch on the burner again, it is necessary to reset the burner control.
Press the lockout reset button (pos.2) for about 1 second (<3 seconds).
After a non-alterable lockout, the red signal lamp in the lockout reset button (pos.2) lights up.
For reset the control box press the lockout reset button (pos.2) for about 1 second (<3 seconds).
GAS XP60CE EVO
GAS BURNERS AT SINGLE STAGE SK071010_2_B
PRODUCT SPECIFICATION
SHORT DESCRIPTION
Burners for gas at single stage.
DETAILED SPECIFICATION
Burner for gas at single stage; composed by:
• Fan at high pressurisationat reverse blades ;
• Combustion head with adjustment at high performance and elevated flame stability equipped with inox steel blast tube and
steel flame disc;
• Flange and insulating gasket for fixing at boiler;
• Three-phase power supply;
• Safety air pressure switch to stop the burner in lock-out in case of failed or anomalous fan operation;
• Gas train with safety valve class A, adjustment 1st stage valve class A;
• Ionisation probe for flame detection;
• IP 40 electric protection level;
• Easy extraction of combustion head without get off the burners by bolier.
CONFORMING TO:
• CE rules;
• 2014/30/UE Directive E.M.C.;
• 2014/35/UE Directive L.V.;
• 2006/42/CE - 2006/42/EG - 2006/42/EC Directive M.D.;
• GAS 2016/426/UE Regulation;
• Reference rules: EN676 (gas) – EN 746-2 (industrial thermoprocessing equipment).
STANDARD EQUIPMENT
• Isomart gasket;
• Flange with insulating gasket;
• Burner nameplate;
• Warranty;
• Instruction handbook for installation, use and maintenance.
OPTIONAL
• Noiseprotection;
• Antivibrationcouplings;
• Handlegastaps.