Datasheet Content
GAS BURNERS TWO STAGES PROGRESSIVE OR
SK073037_E_gb
MODULATING
GAS X5/MCE-EL
Burners for gas modulating (PID fully modulating) if equipped with addition of optional modulation kit and probe.
Composed by: die-cast aluminum body, fan at high pressurisation, combustion head with adjustment at high
efficiency and high flame stability and protection cover with noise reduction plate. Compact overall dimensions
and disposition rationalized of the components with accessibility facilitated for operations of setting and
maintenance.
Available in the versions METHANE (natural gas) or G.P.L. (to specify at the order) on demand specific versions for
town gas, coal gas or biogas.
Gas train complete of: one-block valve class A (1st stage slow opening + safety), minimum gas pressure switch,
filter, stabiliser of gas pressure.
Complete of flange and gasket for installation on generator.
Electronic control box Lamtec BT3 with microprocessor and two servomotors for air and gas adjustment.
Interactive set-up LCD display.
The fuel / combustion air curve, with electronic cam device, is fully exploited, guaranteeing excellent
performance in terms of accuracy and speed, even during the calibration phase. A microprocessor monitors
the different stages of the process and allows the correct repetition of the sequences of operation.
GAS X5/MCE-EL
GAS BURNERS TWO STAGES PROGRESSIVE OR
SK073037_E_gb
MODULATING
TECHNICAL DATA AND WORKING RANGE DIAGRAM GAS X5/MCE-EL
MODEL GAS X5/MCE-EL
Thermal power min. 1°st. / min. 2°st. - max. 2° st.* [Mcal/h] 60/130-300
Thermal power min. 1°st. / min. 2°st. - max. 2° st.* [kW] 69.8/151-349
Gas flow G20 (NATURAL GAS) min 1°st./2°st.-max 2° st.* [Nm³/h] 7/15.2-35
Gas flow G31 (L.P.G.) min 1°st./2°st.-max 2° st.* [Nm³/h] 2.7/5.8-13.5
Fuel: Natural gas (second family) - L.P.G. (third family)
Fuel category: I2R,I2H,I2L,I2E,I2E+,I2Er,I2ELL,I2E(R)
I3B/P,I3+,I3P,I3B,I3R
Intermittent working operation (min. 1 STOP every 24 hours), two stages progressive or modulating
Environmental conditions operation/storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max temperature combustion air [°C] 60
Minimum pressure gas train D1"-S NATURAL GAS/LPG ** [mbar] 27/33
Minimum pressure gas train D1"1/4-S NATURAL GAS/LPG ** [mbar] 16/25
Minimum pressure gas train D1"1/2-S NATURAL GAS/LPG ** [mbar] 13/-
Maximum pressure at the entry of the valves (Pe.max) [mbar] 360
Nominal electric power [W] 540
Fan motor [W] 370
Nominal absorption [A] 2.4
Power supply: 1/N~230V-50Hz
Degree of electric protection: IP 40
Noisiness *** min-max [dB(A)] 66-71
Weight burner **** [kg] 35
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level)
** Pressure of feeding of the gas to the ramp to get the maximum power of the burner considering against pressure in chamber of value
combustion 0 (zero).
*** Measured sonorous pressure in the laboratory combustion, with functional burner on beta boiler to 1 metre of distance (UNI EN ISO 3746 law
-method of control Class 3 - The tollerance of the measured pressure can be taken equal to ± 1 [dB(A)]).
**** For burner with cover in steel (F) to add 4 kg to the weight.
[mbar]
[kW]
[Mcal/h]
Fig. 1 X = Thermal power Y = Pressure in combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN676 standards and are indicative of matching the burner to the
boiler. For the correct operation of the burner bruciatore, combustion chamber dimensions must be in accordance with current regulation. In case
of non-compliance, contact the manufacturer.
GAS X5/MCE-EL
GAS BURNERS TWO STAGES PROGRESSIVE
SK073037_E_gb
OR MODULATING
DIMENSIONS [MM]
Fig. 2 Dimensions
MODEL A B C D E F G O R1 R2 R3 R4 RD Weight
gas train
GAS X5/MCE-EL D1"-S 207 213 98 138 462 310 165 200 160 305 362 515 Rp 1" 6 kg
GAS X5/MCE-EL D1"1/4-S 207 213 98 138 462 310 165 200 160 305 362 515 Rp 1"1/4 6 kg
GAS X5/MCE-EL D1"1/2-S 207 213 98 138 462 310 165 200 170 305 353 605 Rp 1"1/2 8 kg
* SEE "MOUNTING POSITIONS FOR GAS TRAIN"
** SEE "FLAME TUBE LENGTH"
BOILER PLATE
The dimensions of the boiler plate must be as
indicated in the drawing.
Fig. 3 Boiler plate
MODEL L min L max M N min N max
GAS X5/MCE-EL mm 205 226 M10 150 180
FLAME TUBE LENGTH
Flame tube length must be selected based on the specifications supplied by boiler manufacturer and, in any case, it
must be greater than the thickness of the boiler door included its insulation.
In case of boilers with flame inversion or front flue combustion chambers, it is necessary to insulate the area between
the flame tube and front door with refractory material. This protection material must not impede flame tube extraction.
MODEL TC * TL *
GAS X5/MCE-EL mm 250 335
* For different flame lengths, please contact our Technical-Sales Department.
GAS X5/MCE-EL
GAS BURNERS TWO STAGES PROGRESSIVE
SK073037_E_gb
OR MODULATING
PRODUCT SPECIFICATION
SHORT DESCRIPTION
Gas burners modulating (PID fully modulating) if equipped with modulation kit and probe.
DETAILED SPECIFICATION
Gas burner modulating (PID fully modulating) with optional modulation kit and probe, composed by:
• Die-cast aluminum body;
• Fan at high pressurisation;
• Combustion head with adjustment at high performance and elevated flame stability equipped with inox steel blast tube and
steel flame disc;
• Combustible-air adjustment for optimal combustion value;
• Protection cover with noise reduction plate;
• Flange and insulating gasket for fixing at generator;
• Electronic control system for controlling and command the burner;
• Single-phase power supply;
• Safety air pressure switch to stop the burner in case of failed or anomalous fan operation;
• Spherical gas servocontrolled valve: progressive start and free way passage with total opening;
• Servomotor for air shutter;
• Servomotor for spherical gas valve;
• Mobile shutter with total closure when idle for minimize the energetic losses related at boiler cooling;
• Gas train complete of: one-block valve class A (1st stage slow opening + safety), minimum gas pressure switch, filter, stabiliser
of gas pressure;
• Ionisation probe for flame detection;
• IP 40 electric protection level;
• Set up for the additional specific kit that transforms burner operation as modulating i.e.the modulating kit allows to supply any
power between the minimum and maximum value based on instantaneous loading request.
CONFORMING TO:
• CE rules;
• 2014/30/UE Directive E.M.C.;
• 2014/35/UE Directive L.V.;
• 2006/42/CE - 2006/42/EG - 2006/42/EC Directive M.D.;
• GAS 2016/426/UE Regulation;
• Reference rules: EN676 (gas) – EN 746-2 (industrial thermoprocessing equipment).
STANDARD EQUIPMENT
• Isomart gasket;
• Flange with insulating gasket;
• Burner nameplate;
• Warranty;
• Instruction handbook for installation, use and maintenance.
OPTIONAL
• Power modulating kits for temperatures;
• Power modulating kits for pressures;
• Temperature probe 0°C - 400°C (PT 100 ohm at 0° C);
• Temperature probe 0°C - 1200°C (K probe);
• Pressure probe 0-3 bar, 0-6 bar, 0-16 bar, 0-20 bar, 0-30 bar;
• Antivibration couplings;
• Handle gas taps.
The illustrations and data here shown are indicative. F.B.R. Bruciatori S.r.l. reserves the right to bring, without any obligation of warning, any changes that would be appropriate to the continuing development of their products.
GAS X5/MCE-EL