Datasheet Content
Data Sheet
Hermetic filter drier
Type DML and DCL
For uniflow liquid line
All ELIMINATOR® driers have a solid core with
binding material held to an absolute minimum.
There are two types of ELIMINATOR® cores. Type
DML driers have a core composition of 100%
Molecular Sieve, while type DCL contain 80%
Molecular Sieve with 20% activated alumina.
ELIMINATOR® type DML driers are designed for
applications requiring the highest moisture
capacity.
ELIMINATOR® type DCL driers are designed for
applications requiring high moisture capacity
and acid adsorption capacity.
Available with solder (cu-plated steel
connectors) and flare connections.
For other connections please contact your
Danfoss Sales Representative.
AI192386435941en-001401
Hermetic filter drier Type DML and DCL
Features
The Core type DML
• 100% Molecular Sieve core
• High drying capacity minimizing the risk of acid formation (hydrolysis)
The Core type DCL
• 80% Molecular Sieve with 20% activated alumina
• Perfect core blend for systems that operate at high condensing temperatures and require high drying capacity
The Shell
• PED approved for PS 46 bar
• Available with solder (Cu-plated steel connectors) and flare connections
• Corrosion resistant powder-painted finish. Special coating for marine applications available upon request
• Allows installation with any orientation provided the arrow is in the flow direction
• Available in sizes 3 – 75 cubic inches
The Filter
• 25 μm (0.001 in.) filter provides high retention with minimal pressure drop
• Thermally stable up to 120 °C
© Danfoss | Climate Solutions | 2021.03 AI192386435941en-001401 | 2
Hermetic filter drier Type DML and DCL
Application
Intro-diagram
ELIMINATOR® Hermetic filter driers protect refrigeration and air-conditioning systems from moisture, acids, and solid
particles.
With these contaminants eliminated, systems are safer from harmful chemical reactions and from abrasive
impurities.
Figure 1: Application
Danfoss
R64-2107.10
AKS EKC
EVR
TCAE
SGN GBC
DML / DCL GBC
DML Filter drier
Recommended for use with R134a, R404A, R32,R410A,R407C, R23, R600, R600a,R1234yf, R1234ze, R407f,R290,
R452A,R444B, R449A, R448A and R450A refrigerants. Will not deplete oil additives
DCL Filter Drier
Recommended for use with Applicable to R22, R134a, R404A, R32,R410A, R407C, R23, R600, R600a,R1234yf, R1234ze,
R407f, R290, R452A,R444B, R449A, R448A and R450A refrigerants
© Danfoss | Climate Solutions | 2021.03 AI192386435941en-001401 | 3
Hermetic filter drier Type DML and DCL
Product specification
Technical data
Table 1: Technical data
Flare connection Solder connection(cu-plated steel connectors)
Table 2: Surface and volume
Filter drier volume (shell vol‐ Filter drier volume (net vol‐
Filter Solid core surface[cm2] Solid core volume[cm3]
ume)[l] ume)[l]
DML/DCL 03 82 29 0.08 0.051
DML/DCL 05 95 35 0.12 0.085
DML/DCL 08 131 56 0.17 0.114
DML/DCL 16 220 134 0.36 0.226
DML/DCL 30 378 256 0.72 0.464
DML/DCL 41 510 350 0.97 0.62
DML/DCL 60 756 513 1.34 0.827
DML/DCL 75 1019 702 1.81 1.108
Table 3: Acid capacity
Filter Acid capacity(1) [g]
DCL 03 0.5
DCL 05 0.8
DCL 08 1.3
DCL 16 2.9
DCL 30 6.1
DCL 41 8.3
DCL 60 12.2
DCL 75 16.6
(1)
Adsorption capacity of oleic acid at 0.05 TAN (Total Acid Number).
Temperature range:
-40 – 70 °C
Maximum working pressure:
PS 46 bar
Conversions
[1 kg of refrigerant × (Initial PPM of water − Final PPM of water)]
Drops of water =
50
See ARI standard 710-86 for recommended initial and final PPM values for different refrigerants.
Identification
Table 4: Identification
Type Codes Description
Filter drier D Drier
C 80% Molecular Sieve / 20% activated alumina
Solid core
M 100% Molecular Sieve core
Application L Liquid line
© Danfoss | Climate Solutions | 2021.03 AI192386435941en-001401 | 4
Hermetic filter drier Type DML and DCL
Type Codes Description
3 3 in.3
5 5 in.3
8 8 in.3
16 16 in.3
Size (volume) 30 30 in.3
38 38 in.3
41 41 in.3
60 60 in.3
75 75 in.3
2 1⁄4 in. / 6 mm
2.5 5⁄16 in. / 8 mm
3 3⁄8 in. / 10 mm
Connection (filter connection in 1⁄8 of an inch incre- 4 1⁄2 in. / 12 mm
ments) 5 5⁄8 in. / 16 mm
6 3⁄4 in. / 18 (19) mm
7 7⁄8 in. / 22 mm
9 11⁄8 in. / 28 mm
(blank) Flare connection
Connection type
s Solder connection
Example for type codes
D C L 05 3 s
D Filter drier
C Solid core
L Application
05 Size (volume)
3 Connection (filter connection in 1⁄8 of an inch increments)
s Connection type
Selection
Type selection is made considering the application
Table 5: Selection
Refrigerant and oil types DCL DML
HFO Recommended Recommended
HC (1) Recommended Recommended
Refrigerant
HFC Recommended Recommended
HCFC Recommended Recommended
Mineral or AB Recommended Recommended
Oil POE or PAG, pure Recommended Recommended…