Datasheet Content
Series TMV
THERMOSTATIC EXPANSION VALVES
INTERCHANGEABLE ORIFICE CARTRIDGE
PRODUCT DATA
Features
• TMV / TMVBL: with internal pressure equalisation; for
single injection in installations with one or more
cooling circuits
• TMVX / TMVXBL: with external pressure equalisation;
for optimal evaporation effectiveness in all
applications. Obligatory for multiple injection by liquid
distributors
• Combi adsorber charge
The same valve can be used for different
refrigerants (see table on page 2)
Controller charge is high sensitive and responsive
TMVX thus lowest possible level of superheat can be
achieved
Charge is not sensitive to effects of temperature on
the capillary tube and valve head
Damping characteristic results in stable control
behaviour
• Suitable for systems with hot gas defrosting
• Adjustable superheat setting
TMVXBL • Flare connections: TMV, TMVX
• Flare / solder connections: TMVBL, TMVXBL
• Extreme durable due to stainless steel head and
Application stainless steel diaphragm welded using protective gas
• Interchangeable orifice cartridges
Thermostatic expansion valves series TMV are used in
general refrigeration and for original equipment. • Refrigerants: R134a, R401A, R12
R22, R407C, R407A, R422D
Plants with one or more circuits such as refrigerated cabinets
R404A, R507A, R402A, R407B, R502
even with cramped mounting conditions, ice and cream
R410A
machines, milk cooling units, water chillers, vehicle air
conditioning systems, cold stores, and air conditioning
systems. Specification
Nominal capacity range 0.52 to 22.4 kW R22
(small orifice graduation for
Materials optimal control behaviour,
interchangeable orifice
Body brass cartridges)
Thermal head stainless steel Evaporating temperature range see table on page 2
Connection solder: copper Maximum pressure PS see table on page 2
flare: brass Maximum test pressure PF see table on page 2
Max. ambient temperature 100 °C
Max. bulb temperature 140 °C
Static superheat approx. 3 K
Length of capillary tube 1.5 m
Bulb diameter 12 mm
Copyright © 2009 Honeywell GmbH • Subject to change without notice EN0H-1900GE23 R0709
SERIES TMV
Thermal Charges and Temperature Ranges
1. Adsorber charge 2. Adsorber charge with pressure limiting performance MOP
Refrigerant Evaporation PS PF Refri- Evaporation MOP PS PF
temperature (bar(a)) (bar(a)) gerant temperature (bar(a)) (bar(a))
range range
R134a, R401A, +15 °C to -30 °C 34 37.4 R134a, +5 °C to -30 °C MOP A +15 °C 34 37.4
R12 R401A, -10 °C to -30 °C MOP A ±0 °C 29 31.9
R12
R22, R407C, +15 °C to -45 °C 36 39.6
R407A, R422D R22, +5 °C to –45 °C MOP A +15 °C 36 39.6
R407C,
R404A, R507A, ±0 °C to -50 °C 36 39.6 -10 °C to -45 °C MOP A ±0 °C 29 31.9
R407A,
R402A, R407B,
+15 °C to -30 °C 36 39.6 R422D -27 °C to -45 °C MOP A -18 °C 29 31.9
R502
R404A, -10 °C to -50 °C MOP A ±0 °C 36 39.6
R407C +15 °C to -30 °C 36 39.6
R507A,
-20 °C to -50 °C MOP A -10 °C 34 37.4
R410A +15 °C to -20 °C 40 44 R402A,
Further refrigerants on request. R407B, -27 °C to -50 °C MOP A -18 °C 34 37.4
R502
Thermal systems with adsorber charge are completely
insensitive to effects of temperature on the capillary tube and Further refrigerants and MOP on request
valve head. It reacts only according to the temperature of the
bulb.
Thus, Honeywell TMV valves with combi adsorber charge
work absolutely reliable, even in icy condition or while
defrosting using hot gas.
Capacities
Nominal capacity (kW)*
Type Orifice size
R134a R22 R407C R422D R404A R507A R410A
0.3 0.36 0.52 0.50 0.36 0.36 0.36 0.62
0.5 0.69 0.99 0.95 0.67 0.68 0.69 1.2
0.7 1.0 1.4 1.3 0.92 0.97 0.98 1.6
1.0 1.4 2.0 1.9 1.3 1.4 1.4 2.4
TMV
1.5 2.2 3.2 3.1 2.2 2.2 2.3 3.8
TMVX
2.0 2.9 4.0 3.9 2.7 2.8 2.9 4.8
TMVBL
2.5 4.0 5.8 5.6 3.9 4.1 4.1 6.9
TMVXBL
3.0 6.6 9.3 8.9 6.3 6.5 6.6 11.1
3.5 8.7 12.2 11.7 8.3 8.6 8.7 14.6
4.5 11.8 17.0 16.4 11.3 12.0 12.1 20.3
4.75 15.9 22.4 21.6 15.3 15.8 15.9 26.8
* Capacities are based on t0 = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.
Dimensions and Weights
Type Connections Weight
(kg)
Inlet Outlet Pressure
(B) (A) equaliser (C)
TMV 5/8" UNF 3/4" UNF - approx. 0.35
TMVX 5/8" UNF 3/4" UNF 7/16" UNF approx. 0.36
5/8" UNF 12 mm ODF -
TMVBL approx. 0.33
5/8" UNF 1/2" ODF -
5/8" UNF 12 mm ODF 6 mm ODF
TMVXBL approx. 0.34
5/8" UNF 1/2" ODF 1/4" ODF
EN0H-1900GE23 R0709 2 Honeywell GmbH • Subject to change without notice…