Datasheet Content
Specifications Features Quick Start
μBluVac+ Range: 0 – 25,000 Microns, 25 Torr • Hi-Visibility Back-Lit Display 1. Install 2 'AAA' batteries.
3330 Pa, 33.3 mBar, 25 mmHg • Microns, Pascals, Millibar, mmHg, Torr 2. Press and hold for 1 second.
• 0 – 25,000 Micron Range with 1 Micron
Accuracy: 5% of Reading +/- 5 Microns 3. Press and hold to change the vacuum
Resolution
Resolution: 1 Micron (< 1000 Microns), • Automatic Oil Sensor measurement units.
0.1 Pa, 0.001 mBar/mmHg/Torr • Wide Operating Temperature Range 4. Using the supplied coupler, connect the
Warm-up: Instant • Long Battery Life μBluVac+ to an unused service port,
• Calibration Self-Test core removal tool, or hose attached to
Response: Instant
• Calibratable – No Reference Needed the system.
Power: 2 'AAA' Alkaline Batteries
• Ideal for HVAC, Industrial and Scientific 5. Start the vacuum pump. Display will
Lithium Recommended for Low show vacuum pressure in selected
Temperature Operation.
Battery Life: Up to 100 Hours (Bluetooth
Wireless Operation units.
6. Press and hold for 1 second to turn
Off)
Double click to turn the radio on and off. the power off.
Op. Temp. -10F – 122F (-12C – 50C) When turned on, the icon will flash in the
Fitting: ¼” MFL Anodized Aluminum display. This is an indication that the radio is
App Store Google Play Weight: 2.7 oz. (77g) with Batteries on and waiting for a connection from a mobile
(iOS) (Android) app. When a connection is made by a mobile
Dimensions: 4.3” x 1.3” x 1”
app, the icon will illuminate solid (not
(11cm x 3.3cm x 2.5cm)
flashing).
Safe Over- WARNING: To avoid damage, only hand-
Wireless Micron Gauge Pressure: 500 PSI For wireless operating instructions, please tighten sensor connection. If greater torque
refer to the instructions and help material is required, support the sensor housing with a
Wireless
¾” wrench.
User's Guide Range: Up to 100m Line-of-Site included with the iOS or Android app.
Display Hi-Pressure Indication Sleep Mode Range and Resolution
To conserve battery life, the μBluVac+ enters
The µBluVac+ displays “HI-P” when the The μBluVac+ has a broad vacuum
Sleep Mode after one minute in HI-P (unless
vacuum pressure exceeds 25,000 Microns measurement range and very high resolution:
wireless operation is active and connected):
(3330 Pa, 33.3 mBar, 25 mmHg/Torr):
Units Range Resolution
10 (@ > 1,000)
Pa 0 – 3,330 1 (@ > 100)
0.1 (@ < 100)
Full power operation will resume when a 0.1 (@ > 10)
Indicates Calibration Self-Test and Backlight button is pressed, or if the vacuum pressure mBar 0 – 33.3 0.01 (@ > 1)
0.001 (@ < 1)
is reduced below 25,000 microns.
Field Calibration Mode
Press and release to toggle the backlight 0.1 (@ > 10)
Torr Units Selected on and off. To conserve battery power, the Auto Power-Off mmHg
0 – 25 0.01 (@ > 1)
backlight will automatically turn itself off after Torr
0.001 (@ < 1)
Pascal Units Selected one minute. The μBluVac+ powers off completely after
one hour in Sleep Mode. 100 (@ > 10,000)
Millibar Units Selected Microns 0 – 25,000 10 (@ > 1,000)
Power Management Battery Installation 1 (@ < 1,000)
Microns Units Selected
Battery Level Indicator 1. Remove battery cover from the back of the
mmHg Units Selected
instrument.
Four bars in the battery level indicator
Battery Level Indicator 2. Install 2 'AAA' Alkaline batteries observing
indicate full battery strength. The μBluVac+
will turn itself off when the batteries are fully polarity.
Wireless Operation Indicator
consumed. 3. Replace battery cover.
Oil Sensor & Cleaning Calibration Self-Test Calibration Calibration (cont'd)
If oil or other contamination is inadvertently To ensure highest accuracy, periodically To calibrate the μBluVac+: 8. Allow the unit to warm slowly to 20C.
drawn into the sensor, the display will show: perform a calibration self-test:
1. Ensure the sensor is clean and dry. 9. When complete, the display will show:
1. Turn the μBluVac+ power off.
2. Install fresh batteries, place dust cap over
2. Expose the μBluVac+ to atmospheric vacuum port, and turn the power off.
pressure.
3. Insert the unit into a small Ziploc®
3. Press and continue to hold . After 5 (resealable zipper bag) and seal.
To clean the sensor: seconds, the display…