ACM Series
Power Supply/Chargers with
Multi-Output Access Power Controllers
Description
Altronix ACM series distribute and switch power to access control systems and acces-
sories. They convert a 115VAC, 60Hz input into eight (8) independently controlled
12VDC or 24VDC fuse protected outputs. These power outputs can be converted to dry
form “C” contacts. Outputs are activated by an open collector sink or normally open
(NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push
Button, PIR, etc. Units will route power to a variety of access control hardware devices
including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate
in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency AL600ULACM
Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire
alarm disconnect feature is individually selectable for any or all of the eight (8) outputs.
Key Features
- Eight (8) independently controlled outputs. - Fire Alarm disconnect (latching or non-latching) is individually
selectable for any or all of the eight (8) outputs.
Output options:
a) Eight (8) Fail-Safe and/or Fail-Secure power outputs; - Alarm output relay indicates that FACP input is triggered
b) Eight (8) form “C” 5A rated relay outputs;
- Fire Alarm disconnect input options:
c) Any combination of the above.
a) Normally open (NO) or normally closed (NC) dry contact input
- Eight (8) auxiliary power outputs (unswitched). b) Polarity reversal input from FACP signaling circuit.
- Output fuses are rated @ 3.5A. - Built-in charger for sealed lead acid or gel type batteries.
- Filtered and electronically regulated outputs. - Instantaneous transfer to stand-by batteries.
- Supervision: - UL Listed in the U.S. and Canada.
- AC Fail
- Lifetime Warranty / Made in the U.S.A.
- Battery Fail and Battery Presence.
ACM Series Power Supply Configuration Reference Chart
12VDC Total 24VDC Total Individual 115VAC 60Hz Power Supply Power Supply
Altronix Output Output Fused Output Input Board Input Board Battery
Model Number Current Current Outputs Rating Current Draw Fuse Rating Fuse Rating
AL400ULACM
4A 3A 3.5A 15A/32V
AL400ULACMJ
AL600ULACM
6A 6A 3.5A 5A/250V ---------
AL600ULACMJ
8 2.5A
AL1012ULACM
10A --------- 2.6A
AL1012ULACMJ
15A/32V
AL1024ULACM
--------- 10A 4.2A 6.3A/250V
AL1024ULACMJ
Rev. ULACM-01312018
ACM Series
Power Supply/Chargers with
Multi-Output Access Power Controllers
Specifications
Input Agency Listings
Voltage 115VAC, 60Hz. All Models:
Fusing Varies, see Reference Chart. UL:
UL294 Access Control System Units.
Outputs cUL:
Voltage 12VDC or 24VDC, see Reference Chart. CSA C22.2 No.205 Signal Equipment.
Current Varies, depending on the model. AL400ULACM(J), AL600ULACM(J) only:
Protection Fused 3.5A. CSFM California State Fire Marshall Approved.
Auxiliary 3.5A (unswitched).
Other Overvoltage protection. Physical and Environmental
Filtered and regulated outputs. Dimensions (H x W x D)
AL400ULACM, AL600ULACM, AL1012ULACM, and AL1024ULACM:
Back-up Battery (not included) 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).
Capacity 12AH / 12VDC (1 or 2 within enclosure). AL400ULACMJ, AL600ULACMJ, AL1012ULACMJ,
18AH / 12VDC (requires larger “J” enclosure). and AL1024ULACMJ:
40 AH / 65 AH (requires separate enclosure). 18” x 14.5” x 4.625” (457.2mm x 368.3mm x 117.48mm).
Type Sealed lead acid or gel type. Product Weight / Shipping (approx.)
Fuse Rating 15A @ 32VDC Model Product Weight Shipping Weight
AL600ULACM(J) does not have a battery fuse. AL400ULACM 10.7 lbs. (4.85 kg) 12 lbs. (5.44 kg)
Failover Upon AC loss, instantaneous. AL400ULACMJ 14 lbs. (6.35 kg) 15 lbs. (6.8 kg)
AL600ULACM 10.3 lbs. (4.67 kg) 11.6 lbs. (5.26 kg)
Fire Alarm Disconnect AL600ULACMJ 14.85 lbs. (6.74 kg) 17.1 lbs. (7.76 kg)
Latching or non-latching, individually AL1012ULACM 10.7 lbs. (4.85 kg) 12 lbs. (5.44 kg)
selectable for any or all of the eight (8) outputs. AL1012ULACMJ 14.1 lbs. (6.40 kg) 15 lbs. (6.80 kg)
AL1024ULACM 11.75 lbs. (5.33 kg) 13.05 lbs. (5.92 kg)
Supervision AL1024ULACMJ 14.9 lbs. (6.76 kg) 16.1 lbs. (7.3 kg)
AC Failure Form “C” contacts. Temperature
Battery Form “C” contacts. Operating 0ºC to 49ºC (32ºF to 120ºF).
Storage -20ºC to 70ºC (-4ºF to 158ºF).
Indicators (LED) Relative Humidity 85% +/-5%.
Input 115VAC is present. BTU/Hr. (12VDC/24VDC, approx.):
DC Output Powered. Model 12VDC 24VDC
Battery Discharged or not connected. AL400ULACM(J) 25 37
Relays Individual LEDs indicate outputs are AL600ULACM(J) 37 74
triggered (relays energized). AL1012ULACM(J) 61 N/A
FACP Indicates FACP disconnect is triggered. AL1024ULACM(J) N/A 123
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email:
[email protected] | www.altronix.com